Recommendation 1
IOPC recommendationThe IOPC recommends that the Ministry of Justice (MOJ) amends the Police Custody Suites Design Guide to reflect that any sharp edges on metal rebate strips (also known as rectification strips) fitted to custody cell doors should be removed during construction and inspection to lessen any risk of self-harm.
This follows an IOPC investigation into a near-miss in custody. A detainee was placed in a custody cell [redacted] [ and made an ] attempt to harm themselves.
Following the incident, remedial works were conducted on cell doors containing the rebate strips at the custody suite where the incident took place and the NPCC circulated a force-wide notification to custody leads asking them to consider checking any rebate strips – widely fitted to custody doors to minimise ligature risks – and removing the edges where necessary to lessen the risk of a similar incident reoccurring. A review of the existing Police Custody Suites Design Guide showed that it did not contain specific reference to ensuring that sharp edges on rebate strips were removed to lessen any self-harm risk during construction or inspection.
Recommendation accepted:
Additional guidance has been added to:
Police Custody Suites Design Guide
Standard Number STD/Z/DG/078
Issue 003 – Publication Date: 06/02/2023
Section 8.11.4 Cell Door
New text added (as bold underlined):
“The cell door frame should be fitted with a removable and adjustable door keep. This will allow the door to be quickly opened should the lock jam and allows the tolerance fit against the rebate to be adjusted. The tolerance between the cell door and rebates (from the cell side) is critical and should be within the advised limit of 2mm and be capable of adjustment as required during the operational use of the cell in years to come. The gap between the bottom of the door and floor should be a maximum of 10mm. It is important that the inner (cell-side) face of the door, frame and rebate strip are carefully inspected for any sharp edges or angles that a detainee might use to cut or abrade materials or themselves and that any such edges are removed.”
Section 18.5.14 Custody suite inspections prior to practical completion
Text added to checklist (as bold underlined):
“Typical checklists: Each force should maintain a checklist of features to be inspected.
- Cell doors – particular attention to be given to max gaps [2mm] at door stops & hatch, [10mm] between door and floor, sharp edges on rebate strips or other components”